Distributed Control Systems Configurations
This section gives guidance for configuration in a DCS application. Figure 36 gives two
generalized drawings that cover DCS applications to ensure switch safety.
Figure 36 DCS Switches Wiring Options
Configuration Considerations
A typical value for 24 AWG cable about 0.025 Ohm/ft (see Wiring Option #1)).
If IS barrier is a combination of fuse, resistor and Zener diode then the connection is
shown in Option #2. The barrier must have adequate resistance to limit inrush current,
as the fuse cannot limit inrush current (see Wiring Option #2).
Power source can be part of
DCS/PLS card. Power source
requirements: V
30 V. I
max
1 A.
SVI
Switch
Add resistor so load with
resistance
≥
30 (including
wire resistance)
+
-
Negative switch pole
must be
directly wired to negative pole of power supply.
+
-
Wiring Option #1
SVI
Switch
Add resistance sized to
limit in-rush current < 50
mA.
+
-
+
-
Wiring Option #2
Power source can be part
of DCS/PLS card. Power
source requirements: V
30 V. I
max
1 A.
Any load. Power source is not directly
connected to the switch.
Load can be a circuit within DCS/PLS
card, between power source and
switch.
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......