Masoneilan SVI FF Instruction Manual
=
|
213
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
C. Setting Environment Settings
Configure the
Network Management
parameters manually (the optimal configuration may
result in values different from recommendations):
Open the
Environment
settings and verify that
Make NM Parameter the optimum value
checkbox is not selected (Figure 73).
Figure 73 Environment Settings
D. Adjust the Communication Parameter . . .
WARNING
Changing Network Management Communication parameters
stops execution of ALL control devices on this segment until the
new parameters are downloaded and the segment schedule is
re-initialized.
Review the use of all instruments on the segment and take
necessary steps to ensure safety of all control loops and safety
applications related to the segment.
1. Open the
Fieldbus Builder
and select from the main menu
Tools->Adjust Communication
Parameter. . .
2. Open the
Parameter Edit
window and select the
Segment->Common-NM
from the device
list.
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......