Figure 111 Transducer Block Open/Close Action vs Final_Value
Standard DD-based Configuration Tool: Transducer Block - Fail Action
Parameter
Using this method swaps the closed and open fail positions for the valve. Table 39 lists the
Final_Position_Value
for each configuration and Figure 112 illustrates its workings.
You can use a tool such as a DCS configuration station or a handheld to configure the valve in
Normal Action
or
Reverse Action
by setting the transducer block parameter
ACTUATOR_3.ACT_FAIL_ACTION
Figure 112 Transducer Block - Fail Action Parameter