Masoneilan SVI FF Instruction Manual
=
|
177
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
END_POSITION (2)
60
Any
Applicable to: All
Start position for the test. May be above or below End
position.
Range is -5 to full open +5.
Applicable to open loop signature: Start and End Positions
must be more than 20% different.
SET_POINT_RATE (3)
5
Any
Applicable to: Ramp test and Signatures.
0.5-100.1 %/s.
SAMPLING_TIME (4)
10
Any
Applicable to: Step test.
2 to 60 s.
DIRECTION (5)
0
Any
Applicable to Diagnostic signature, Ramp test:
0. Both ways (from Start position to End position and
back).
1. One way (from Start position to End position).
OPTION (6)
0
Any
Applicable to Diagnostic signature:
0. Open loop.
1. Closed loop.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description