Troubleshooting Communications
Table 23 Troubleshooting Communications
Problem
Presumed Cause
Remedy
See Section
Communication with the SVI
FF cannot be performed.
Wiring is incorrect.
Correct wiring.
“Wiring the SVI
FF” on page 65
“System Con-
figuration” on
page 106
The power is off or the power
supply voltage is less than 9 V.
Supply proper voltage.
“Wiring the SVI
FF” on page 65
“Physical and
Operational
Specifications”
on page 95
The address detection range is
not correctly set.
Correct address detection
range.
“Step 4: Set Tag
and Address” on
page 32
Communication with the SVI
FF is frequently cut off.
The fieldbus is experiencing a
large amount of noise.
Missing terminators on the bus,
incorrect terminator placement
or extra terminators. Refer to
FOUNDATION Fieldbus specifi-
cations for a full discussion of
terminator requirements.
Using an oscilloscope,
check the waveform on the
fieldbus.
—
The SVI FF can be detected,
but neither function blocks
nor transducer block can be
seen.
The node address of the SVI FF is
left in the default (0xF8-0xFB).
Change the device to an
operable address. See the
descriptions for address
settings.
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......