The display mode also can be changed remotely from a DD based host. To switch the
display back to normal:
1. Open the device editor in connected mode and navigate to the Transducer block.
2. Verify that the block is in LO mode.
3. Set Target mode to
Manual
to avoid valve movement when the mode is switched.
4. Observe the state of the display/position control by reading
86.APP_MODE
parameter – it
should have a value of
Setup
(Figure 109).
Figure 109 86.APP_MODE Parameter
5. From the drop-down menu select
Normal
(Figure 110).
Figure 110 Select Normal Mode
6. Write the changed value of
APP_MODE
parameter to the device. You can verify success by
noting that the mode in is now not
LO
.