Modifications reserved
Page 66/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
Autonomy times for lead acid batteries (VRLA)
192 cells
Autonomy at full load at PF=0.8
U floating = 436 Vdc (2.27 Vdc - cell)
Battery with expected trickle life 5 years
Battery with expected trickle life 10 years
UPS model
10Ah 17Ah
24/26
Ah
33Ah 38Ah 65Ah
2x38
Ah
75Ah 100Ah 150Ah 200Ah 300Ah 400Ah 500Ah
SitePro 10 kVA
9 16 30/31 45 52 105 - 135 -
-
-
-
-
-
SitePro 15 kVA
- 11 15/16 26 32 62 - 84 117 -
-
-
-
-
SitePro 20 kVA
- 6 10/11
18 22 42 - 58 84 135 - - - -
SitePro 30 kVA
- - 5/6 11 12 27 - 36 50 84 117 - - -
SitePro 40 kVA
- - - 6 7 18 - 24 6 58 84 135 - -
Stop Operation time
Residual battery autonomy time before UPS forced shutdown.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells
Number of cells of the battery.
Lead-Acid (VRLA):
177
÷
192 cells
NiCd:
281 cells
Boost:
182
÷
195 cells
Example:
180 battery cells
30 blocks / 12 Vdc battery
60 blocks / 6 Vdc battery
180 blocks / 2 Vdc battery
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery manufacturer.
`
Configuration
CONFIGURATION
Save and exit ?
Yes
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done
only from a GE SERVICE PERSON as it requires an access code.
Continue
►