Modifications reserved
Page 46/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
7.2 METERING
The
METERING mode
is entered any time the “
METER
” key is pressed.
The
LCD screen
will indicate a series of screenshots showing the measures of all electric parameters like
AC, DC and various statistics.
In this mode the keys perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
It is possible to view any key functional description by pushing the key for more than 3 seconds.
`
Home\Meter
BATTERY
V 409
V
I 5.0
A
T +25°
C
Charge level
80 %
Autonomy 12
Min
Battery data screen
V
The battery voltage.
I
The battery current (negative values correspond to
the discharge of the battery).
T
The temperature of the battery (“SENSOR DISABLE”
indicates sensor disabled).
Charge level
The battery charge level.
Autonomy
The estimated backup time with the
present load.
`
Home\Meter
RECTIFIER
f : 50.0 Hz
L12 :
397 V
Vdc
:
409 V
L23 :
395 V
Idc1
:
41.0 A
L31 :
393 V
Idc2
:
0.0 A
Rectifier mains data screen
f
The input frequency of the rectifier.
L12
L23
The voltage levels between the three phases (line-
L31
to-line).
Vdc
Rectifier voltage output.
Idc1
Output current rectifier bridge.
Idc2
Output current 2
nd
Rectifier Bridge
(optional 12
pulse
Rectifiers
only).
`
Home\Meter
MAINS
f 50
Hz
L1 230
V
L2 229
V
L3 231
V
BYPASS FREE
Bypass mains data screen
f
The frequency of the mains.
L1
L2
3-phase mains voltage PHASE /NEUTRAL.
L3
Bypass
Bypass status: FREE / LOCKED.