Modifications reserved
Page 79/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
5. Open the manual bypass switch Q2 (Pos. 0) on all UPS units.
LED 9 (manual bypass Q2) is Off.
The
load
is supplied by the mains through the
automatic bypass
.
6. Insert the inverter by pressing
“
Inverter ON
”
( I ) key on first UPS unit
.
The
inverter
will start up.
LED 5 (inverter)
must be blinking.
In a short time, when the
inverter voltage
is confirmed, the
LED Inverter (5)
will stop blinking and stay fixed
lit.
In case of sufficient output power, the output will transfer to
Inverter
.
LED Alarm
turn Off and the
LED Operation
must be lit.
The
synoptic diagram
, on first UPS unit, must display the
status
“
LOAD SUPPLIED BY INVERTER
”
.
7. Insert the inverter by pressing
“
Inverter ON
”
( I ) key on all other UPS units.
Do not start the next
Inverter
until the sequence of the previous ends.
As soon as the output power of the
inverters
is sufficient to supply the
load
, the output of the units with
running
inverter
will transfer to
inverter
.
LED Alarm
turn Off and the
LED Operation
must be lit.
The
synoptic diagram
, on all UPS units, must display the
status
“
LOAD SUPPLIED BY INVERTER
”
.