Modifications reserved
Page 58/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
`
Home\Setup\User
DISPLAY
UPS name
:
SitePro
Language :
ENGLISH
V
LCD Display screen
UPS Name
The user can choose the name of the UPS
model shown on the main page (max. 9
characters).
Language
This parameter allows the choice of
language used to display the information.
Valid choices are:
English, German, Italian,
Spanish, French, Finnish, Polish, Portuguese,
Czech, Slovakian, Chinese, Swedish, Russian
and Dutch
.
`
Home\Setup\User
SUPER ECO MODE
Enabled :
N
DAY OF WEEK
d1 d2
d3
d4
d5
d6
d7
HOURS / DAY
24 24 12 12 12 12 12
SUPER ECO MODE screen
This screen is enabled only for a single UPS, not for an
RPA
Parallel System
.
Enabled
This parameter (values
Y
/
N
) enables or disables the
operation in
SEM mode
(Super Eco Mode)
.
If the value is
Y
and the current time is in the interval for the
current day, the
SEM mode
is active.
The activation / deactivation of
SEM
mode is indicated each time in the event list.
In order to check the
inverter
function, at least
1 minute
of
VFI
mode must be programmed during the week (the
Y/N
parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in
VFI mode
is not respected, the
SEM mode
will be disabled.
If the value is
N
, the UPS is normally operating in
VFI / double conversion mode
at all times.
DAY OF WEEK (d1 ÷ d7): Enabling time in function of weekdays
For the weekdays from
d1
to
d7
(Saturday to Friday)
the edit mode (edit day) allows to define time intervals when
the UPS is operating in
SEM mode
.
The hour is given in 24-hour format.
These intervals are defined by:
SEM START
:
The hour of the day after which the
SEM mode
is enabled.
The
SEM mode
is enabled until the following
SEM STOP
time is reached (the
SEM STOP
time of
the same day if this is later than the
SEM START
time, the
SEM STOP
time of the following day
otherwise).
SEM STOP
:
The hour of the day before which the
SEM mode
is enabled.
The
SEM mode
is enabled starting from the preceding
SEM START
time (the
SEM START
time of the same day if this
is earlier than the
SEM STOP
time, the
SEM START
time of the previous day otherwise).
Identical times for
SEM START
and
SEM STOP
maintain the existing mode only in case the previous command was
SEM START
and the following command will be
SEM STOP
.
HOURS / DAY
:
The number of
SEM mode
hours per weekday (from
d1
- Saturday
to
d7
- Friday
) is displayed in the operation
mode parameter window (ceiling value).