Modifications reserved
Page 77/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
8.2.2 Parallel UPS shutdown with load transfer on manual bypass Q2
NOTE !
Not following this procedure can cause protected loads to shut down!
Never close or open either
Q1
or
Q2
with the inverter running!
Initial situation: the load is powered by all
inverters
of the
Parallel System
.
The complete
UPS Parallel System
has to be turned OFF, while providing the
load
power by
mains
through all
manual bypass switch Q2
of the
Parallel System
.
With the
UPS Parallel System
in normal operation and the
inverters
supplying the
load
,
the switches
Q1
and
Q4
are closed (Pos. I),
Q2
are open (Pos. O)
and the
battery fuses F8 – F9
are inserted
.
The
synoptic diagram
, on all UPS units, must display the status
“
LOAD SUPPLIED BY INVERTER
”
.
1. Disconnect the inverter by pressing
“
Inverter OFF
”
( O ) key and hold until the LED Inverter (5)
turns OFF on all UPS units.
At no redundancy, the system will transfer to
mains
supply.
LEDs Alarms
are lit and the
LEDs Operation
are Off.
The
synoptic diagram
, on all UPS units, must display the status
“
LOAD SUPPLIED BY AUTOMATIC BYPASS
”
.
2. Close the manual bypass switch Q2 (Pos. I) on all UPS units.
LED 9 (manual bypass Q2)
lights up on all UPS units as soon as the first switch
Q2
shuts down
Load
is now supplied from
mains
in parallel from
automatic bypass
and
manual bypass Q2
of all UPS units.
3. Open the output switch Q1 (Pos. 0) on all UPS units.
The
load
is now supplied only through the
manual bypass Q2
.
4. Press “Load Off” key on all UPS units.
The output contactor
K6
open and
LED 8 (load on automatic bypass)
is OFF.
5. Open the input rectifier switch Q4 (Pos. 0) on all UPS units.
The
acoustical alarm
is activated, press
“MUTE”
key to reset it.
6. Disconnect the battery removing the battery fuses F8 – F9 on all UPS units.
The electronic boards and the control panel are still powered from AC power supply through the plug
X8
on
the
”P1 - Power Interface”
(Warning! This board will remain powered from the mains throughout this
procedure!).
The
acoustical alarm
is activated, press
“MUTE”
key to reset it.
The
load
is now powered directly by
mains
through all
MANUAL BYPASS Q2
.
WARNING!
It will take 5 minutes for the DC capacitors to discharge
Open only the front door, do not open any other part of the UPS.