Operating Manual
SitePro 10-15-20-30-40 kVA / S8
Code
Message
Meaning
4562
DETOUR ON
The auxiliary contact indicates that manual bypass Q2 was
closed.
4564
DETOUR OFF
The auxiliary contact indicates that manual bypass Q2 was
opened.
4567
COMMAND LOAD ON MAINS
The control unit received a command to transfer the load on
mains.
4568
COMMAND LOAD ON INVERTER
The control unit received a command to transfer the load on
inverter.
4572
NO MORE OVERLOAD
End of the overload condition detected with alarm 4570.
4580
INVERTER AND MAINS
SYNCHRONIZED
The voltages of Inverter and mains bypass are
synchronised.
4582
COMMAND NOT
TO SYNCHRONIZE
Command not to synchronise with mains has been done for
mains BP out of tolerance (4410) or setting parameters.
4583
COMMAND TO SYNCHRONIZE
Command to synchronise with mains has been done for
mains BP OK (4411) or setting parameters.
4600
COMMAND UPS ON
The SEM mode function has been disabled or the
programmed time is expired.
The UPS returns to VFI mode supplying the load normally by
inverter.
4601
COMMAND UPS STANDBY
The function SEM mode is enabled, and according to the
time program the UPS will run in SEM mode, supplying the
load normally by mains.
4602
Q1 OPEN
The auxiliary contact indicates that the output switch Q1
was opened.
4603
Q1 CLOSED
The auxiliary contact indicates that the output switch Q1
was closed.
4699
BATTERY TEST IMPOSSIBLE
Not possible to start battery test (is postponed):
-
No mains rectifier or bypass.
-
Battery not fully charged.
-
Load is below 10% or above 80%.
4763
REMOTE CONTROL ON
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.
.
4764
REMOTE CONTROL OFF
Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.