CFN Series System
4-4
03/07/03
PROFIT POINT CONSOLE (OPTIONAL)
1.
Verify that the Profit Point and any optional equipment is located in an office type
environment and is correctly installed according to the
Site Controller II or Profit Point
Installation Manual
.
2.
Verify that the AC power cord for the Profit Point is directly connected to the output of the AC
Surge Protector Strip (C01218).
3.
The RS-485 converter must be installed as described below. If you are locating the Profit
Point more than eight feet from the Site Controller, you must use two additional RS-485
junction boxes to connect the devices.
A modular cable must be directly connected to the modular jack port on the back of the Site
Controller labeled
CONSOLE
. The other end of the modular cable is connected to one of
the modular jacks on the converter. The converter is connected to the Profit Point port
SERIAL1
via a 25-pin to 9-pin cable. The converter power supply must be plugged into the
same AC Surge Protector Strip (C01218) as the Profit Point.
POS Distribution Box (POS D-Box) is connected via a 9-pin cable from the
Serial2
port on
the Profit Point to the
Serial2
port on the D-Box. If the site has a PIN Pad, the
Serial3
port of
the Profit Point will be connected to the
Serial3
port of the D-Box. The D-Box power supply
must be plugged into the same AC Surge Protector Strip (C01218) as the Profit Point.
CASH DRAWER
is connected via a 9-pin D-type connector from the cash drawer to the
CASH DRAWER
port on the back of the POS D-Box.
CUSTOMER DISPLAY
must be installed according to the
Site Controller II or Profit Point
Installation Manual
. Verify that the Customer Display is connected to the 9-pin
CUSTOMER
DISPLAY
port on the POS D-Box.
4.
Optional equipment connection:
RECEIPT PRINTER
connection depends upon the type of receipt printer ordered. For a
parallel printer, the printer cable is connected to the D-type 25-pin female connector
PRINTER
on the back of the Profit Point. For an RS-485 printer, the modular cable is
connected directly into the RS-485 jack on the converter. The receipt printer must be
plugged into the same AC Surge Protector Strip as the Profit Point.
PIN PAD
must be installed according to the
Site Controller II or Profit Point Installation
Manual
. Verify that the PIN pad is securely connected to the
PIN PAD
port located on the
POS D-Box.
SCANNER
must be installed according to the
Site Controller II or Profit Point Installation
Manual
. Verify that the Scanner is securely connected to the 9-pin
SCANNER
port located
on the POS D-Box. If a scanner is used that needs external power, it must be plugged into
the same AC Surge Protector Strip as the Profit Point.
Summary of Contents for CFN Series
Page 1: ...CFN SERIES SITE CONTROLLER II ISLANDER II START UP MANUAL C01665 GASBOY INTERNATIONAL LLC ...
Page 2: ......
Page 8: ...CFN Series System Contents 4 03 07 03 ...
Page 24: ...CFN Series System 2 12 03 07 03 ...
Page 25: ...Site Information 03 07 03 2 13 ...
Page 26: ...CFN Series System 2 14 03 07 03 ...
Page 38: ...CFN Series System 4 6 03 07 03 ...
Page 56: ......
Page 58: ......
Page 72: ......
Page 82: ...CFN Series System 9 10 03 07 03 ...
Page 104: ...CFN Series System 12 12 03 07 03 ...
Page 108: ...CFN Series System 13 4 03 07 03 ...