Temperature
Operation
-10 to 60°C
Storage
-20 to 70°C
Transport
-20 to 70°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical Properties
Dimensions
Width
190 mm
Height
198 mm
Depth
31 mm
2.3.2.2 Wiring:
Unshielded Lines:
All unshielded lines must be relieved of tension by using a cable tie to secure to the grounding
plate.
Shielded Lines:
A central ground connection is available to effectively deflect interference. All cable shields must
by connected to ground with good conductivity using a cable tie on the grounding plate or some
other method.
Grounding:
The connection to ground potential must be as short as possible and sufficiently
strong (≥4 mm²).
Figure 13 explains the wiring diagram for the IO module. The following should be considered when wiring:
1) Good Conductive connection to the metallic and grounded rear panel.
2) Connect the braided shield wrapped with conductive foil to the grounding plate using cable ties.
Figure 13: IO Module Wiring