13-17-621 Page 135
C.130
Warning
Cell-Data
importer task
error
An error occurred when
trying to import
diagnostic data from the
iConn unit.
Check the power cable to the iConn and the USB
cable between the iConn and controller. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.131
Warning
Cell-Data
exporter task
error
An error occurred when
trying to export data to
the iConn unit.
Check the power cable to the iConn and the USB
cable between the iConn and controller. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.132
Information
User blocked
due to too many
failed login
attempts
Too many failed login
attempts have occurred.
The user has been
blocked for 30 seconds
after five failed attempts.
Attempt to log in with the correct passcode. If you
do not have the passcode, log in with the next
higher user level and reset the passcode for the
user level with the lost passcode.
C.133
Warning
Import
Hardware-
Configuration
has failed.
An error occurred trying
to load the hardware
configuration file for the
system.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.134
Information
New Hardware-
Configuration
imported
Informational. Hardware
configuration was
successful.
No action needed
C.135
Information
Hardware-
Configuration
was changed
externally
The hardware
configuration was
changed and is no longer
synchronized with the
hardware.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.136
Fault
Error in IO
Mapping task
An error occurred in
trying to load the IO map
for the controller.
Possible
misconfiguration.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.137
Fault
Internal
Configuration
Fault - Bad VFD
Address
A misconfiguration was
detected where one of
the VFDs in the system
is assigned an invalid
address.
Check the configuration and definition files that
have been loaded and ensure that they match the
machine. Reload if necessary. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.138
Fault
Error
Communicating
with Precision
Mixing Valve
Error in Modbus
communications with
precision mixing valve.
Check the RS485 connections between the
controller and the mixing valve. Ensure that the
cable shields are terminated properly. Check for
loose connections. Check to make sure that the
PMV has power.
C.139
Warning
Error on the
PRJ variable
Tasks
An error occurred
loading the project info
task. Internal software
issue.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.140
Warning
Error on Serial
Data model task
An error occurred
loading the data model
task used to supply data
to external
communication
protocols. Internal
software issue.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.141
Warning
Error on Modbus
Data model task
An error occurred
loading the data model
task used to supply data
to external
communication
protocols. Internal
software issue.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.