IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
50
The four access level default settings are:
Access level 1 = Ack.
Access level 2 = Ack., Sig. Sil., Reset, Drill
Access level 3 = Ack., Sig. Sil., Reset, Drill, Det. test, WalkTest, Bypass
Access level 4 = Programming
Default passwords for the access levels are:
Password 1111 = Access level 1
Password 2222 = Access level 2
Password 3333 = Access level 3
Password 4444 = Access level 4
∆∆∆∆
WARNING !
When the system is in access level 4, programming, the system
will not recognize an alarm or trouble condition. The premises
should be protected by a fire watch or other reliable measure(s)
whenever the system is being programmed.
Password Entry
1. Press "Password" keypad switch. Figure 5 is now displayed.
Line 1
Line 2
Line 3
Line 4
Password Entry Screen
Enter Password:
Security Level: X
User ID: XXX
Figure 5
2. To change access levels, enter the appropriate password on the keypad.
3.
To modify the SmartStart program after a system configuration, enter the password access
LEVEL 4.
Û
NOTE: System will reset out of Programming mode after 5 minutes of inactivity.
____________________________________________________________________________________________
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...