IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
17
6. Use the up/down arrow keys to select the circuit of the devices to be bypassed.
>>NOTE: Use the right arrow key to place the cursor under the device address.
7.
Use the up/down arrow keys to select the device address. When the device address is
selected, the device type, zone type and zone status will be displayed automatically.
8.
Use the left/right arrow keys to move to the Bypass status field.
9.
Use the up/down arrow keys to select "NOT ByPassed" or "ByPassed" option.
10. Repeat steps 3 through 6 for each device to be Bypassed.
11. When all desired input devices have been selected - press "
Enter
".
12.
Repeat steps 3-8 to bypass outputs.
13. Press the Enter key. Then exit the test menu by depressing 0, then Enter.
In the same manner as above, Select I/O Groups [2] and/or Circuits [3] for
ByPass.
14. The system will now flash the Acknowledge and Trouble LED’s and the sounder will
activate. Once the system has been acknowledged the Trouble LED will remain flashing
until all bypassed devices are cleared. The display will indicate that a part of the system has
been disabled. Figure T10 is now displayed.
Status: FAULT
xx/xx/xx xx:xx
System I/O’s Bypassed
Figure T10
15. To reactivate Bypassed devices repeat steps 1-11 toggling each device to the “NOT-
BYPASSED” selection.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...