IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
96
G:
lnput group number (F610/F632/F650 only)
A
: Detector average (F610/F632/F650 Apollo Detectors only)
if D=6,14 ie Thermal detector then A=average temp
if D=3,5,11,13 ie Photo,lon then A=average count
S:
Detector variables (F610/F632/F650 Apollo detectors only)
if D=6, 14 ie Thermal detector then S=alarm temp in °C ((S X 2) -10%)+32 = Alarm
Temp in °F)
if D=3,5,11,13 ie Photo,lon then S=sensitivity (0= High , 3 = Low Sensitivity)
C:
lnput device variable
if D=0 ie conventional zone
C
=0 no end of line resistor
C
=1 end of line resistor exists
if D=6, 14 ie Thermal detector then if
C
=1 Rate of Rise ON
C
=0 Rate of Rise OFF
If D=3, 5, 11, 13 ie Photo lon then if
C
=1
Auto compensation
is ON
C
=0 Auto compensation is OFF
Z:
Zone type
Supervisory zone
0=Supervisory zone
1 =Generic zone
Security zones
2=Passive Entry/Exit Security zone
3-Active Entry/Exit Security zone
4=Normal Security zone
5=Active Security zone
Switch zones
6=Activate/Deactivate Security zone
7=Acknowledge zone
8=Drill zone
9=Reset zone
10=Signal Silence zone
11=Abort zone
12=Dump zone
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...