IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
19
Input Test
The Input test function allows the user to individually test the functionality of
each device, operation and response.
Device LED will illuminate if selected for Input Test. The LED will turn off
when the device is deselected.
Function Programming
1=Walk Test 2=Bypass 3=Input Test
4=Output Test 5=Display 0=exit
>3
Figure T2
1.
Press
“
3
” and then “
Enter
”
2.
Figure T3 is now displayed.
CKT:XX Add:XXX D_Type:XXX Counts: XX
Figure T3
CCT
Circuit of selected device (1-4)
Add:
Address of the selected device
D_Type
Device type (
see table P3 in programming
section)
Counts
Real time analog value
3.
Use the up/down arrow keys to scroll through the connected devices. When the device
address is selected, the device type and real time analog value will be displayed
automatically.
4.
Determine the functionality and operating response of the Detector using the following
table.
5.
To exit the Detector Test Mode press the Enter key at any time.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...