IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
14
Walk Test Prog Menu
1=Inputs 2=Inputs/Sig 3=Devices
4=Clear 0=Exit
1=Inputs
Places all inputs in Walk Test
2=Inputs/Sig
Places all Inputs and Signal Circuits in Walk Test
3=Devices
Allows individual selection of Inputs and Signal circuits to placed in Walk Test
through the following procedures..
Figure T5 is now displayed. Use the up/down arrow keys to select the circuit of the
devices to be tested.
>>
NOTE: Use the right arrow key to move the cursor under the
device address.
CKT:XX Add:XXX D_Type:XXX Z-Type:
XXX
Input: NOT IN WALK TEST
Figure T5
4.
Use the up/down arrow keys to select the device address. When the device address is
selected, the device type, zone type and zone status will be displayed automatically.
5.
Use the left/right arrow keys to move to the Walk Test status field.
6.
Use the up/down arrow keys to select "NOT in Walk Test" or "In Walk Test" option.
7.
Repeat steps 3 through 6 for each device to be tested.
8.
When all desired devices have been selected - Press "
Enter
".
9.
The system will now prompt you for a signal circuit to select for Walk Test annunciation.
>>
NOTE: The system will display addressable relay modules that
are not available for walk test mode.
CKT:XXX ADD:XXX D_TYPE: SIG
Output: NOT IN WALK TEST
Figure T5B
9A. Signal circuits are numbered by their physical location in the system. Use the up/down
arrows to select circuits sequentially or enter the circuit number with the alphanumeric
keypad and press enter.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...