IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
3
GENERAL
Identiflex 600 Fire Alarm Control Panel firmware, version r7 is an update of the prior versions of IF 600 FACP firmware.
The version r7 provides all of the features and performance of the previous IF 600 firmware as well as many new features
and improved panel configuration data storage. The version r7 firmware can be used in existing IF 600 systems, including
IF 610, IF 632, IF 630, and IF 650. Because the structure of the Panel Configuration files has changed in revision 7, this
revision is not backwards compatible with version 6 or version 5 and earlier. To upgrade an existing IF-600 panel it is
necessary to either convert the Configuration file using the Gamewell Lap Top program, or completely reprogram the
panel.
NEW FEATURES
SmartStart Password
With the exception of the automatic SmartStart which occurs when firmware chips are installed in an
IF-600 panel, a level 4 password is required to initiate a SmartStart.
Releasing
Provides a multi-step releasing sequence with ANDed inputs, and programmable Pre-release, Abort and Dump.
Water Zone
Allows inputs to be designated as Water Flow with programmable delays, and selectable silencing.
Daylight Savings time
Allows automatic correction of the time for the entry and exit from daylight savings time.
Leap Year
Allows the automatic correction of the date for Leap Years. (Including the year 2000)
Positive Alarm Sequence
Allows Day/Night control of the use of PAS.
Verification Counter
Provides a tally of the number of times a Verification point activates without going into alarm, within the past 30
days. A programmable limit will place a point into trouble if the tally for that point exceeds the limit.
Alarm, Supervisory, Trouble Displays
Allows the selectable display of Alarms, Supervisories, or Troubles.
All Input Walk Test
Allows the placement of all inputs and outputs into walk test without individual programming.
Expanded RAN/SAN Supervision
Allows the supervision of up to 20 RAN/SANs connected to the panel.
Auto Silence Timeout
Allows the timeout for Auto Silence to be programmed.
Silence Inhibit
Allows the inhibit time for Signal Silence to be programmed.
Building Control Switch Supervision
Allows the switches on Building Control Displays to indicate Trouble if they are not in the Auto position.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...