IdentiFlex 630 Installation and Operation Manual
S
mart
S
tart Capable
9-25-96
84
ChangeMenu 2
Change Menu 2 has options to change the City Tie operation, the Automatic Signal Silence
Timer, The Annunciator Supervision, The Trouble Relay operation and the Automatic
Dialer connection.
Change City
The City Tie Circuit is designed to operate in two modes of operation; Standard mode and
Chicago mode. In the Standard mode alarms and troubles are transmitted over the city tie
circuit. In the Chicago mode the City Tie transmits all troubles and alarms with the
exception of City Tie troubles. If the City Tie circuit detects a trouble condition the Spare
relay will transfer for use with a local indicator. That indicates troubles and alarms can’t be
transmitted.
Change Menu (Misc.)
1=Menu1 2=Menu2
0=Exit
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>1
Press Enter Key To Exit
Press Any Other Key To Toggle
City Tie Is In Standard Mode
City Tie Is In Chicago Mode
Change Sig Sil
The Sig Sil option allows the user to set the Signal Silence delay. This is the length of time
the signals circuits will operate before automatically silencing when selected.
EXAMPLE: Entry of the number 3 would equal 90 seconds (3 x 30 sec.= 90sec.)
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>2
Sig Sil Delay Is Set To:0 Min
Delay = Entry (0-10) x 30 Sec
Enter New Sig Sil Delay (0-10):
Change Ann
The Change Ann option allows the user to enable and disable the supervision of the
supervised devices connected to the RS-232 port.
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
Press Enter Key To Exit
Press Any Other Key To Toggle
Remote Annunciator is Detached
Remote Annunciator is Attached
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...