PULSE Installation, Commissioning and Servicing Manual - Revision 19
15.16 Setting a Password - PASSWD
Both the Service Agent password (Level 2) and the Manager password (Level 1) can be
altered.
Once set, if the password is forgotten, Gallagher will only be able to reset to
default when provided with the serial number of the Central Controller.
While it is the responsibility of the site to manage passwords, Gallagher Technical Support
have a mechanism for recording alternate passwords if they are informed of the changes.
C
C
D
PASSWD
LEVEL1
L
L
PASSWD*
C
L
CONFIRM*
C
L
PASSWD
OK
C
L
OFF
ATPM
C
L
VR2
ACTIVE
To change a password:
Use the cursor keys
4
and
6
to select the password level.
LEVEL 1
= Manager Mode or
LEVEL 2
= Service Mode
Press
F
(
PASSWD*
shows edit mode)
Enter password (EG: 123456)
Press
F
(shows
CONFIRM*
) or
to cancel
Re-enter the password (EG: 123456)
Press
F
to confirm or
to cancel (shows
PASSWD OK
- password
has been changed)
This will set the password for both sides of the dispenser.
Repeat for each dispenser.
Lost passwords can make dispenser servicing impossible. Do not change passwords
unless a reliable system of recording a change is in place.
15.17 Setting VR Active - VR2
For non-VR sites VR Control can be set as either
ACTIVE
or
OFF.
VR menu items are VR2 and ATPM (Automatic Tank Pressure
Monitoring).
For VR equipped sites both VR Control items must be set to
ACTIVE.
VR Control can be set to
OFF
to disable alarms and forced
shutdown. This will enable servicing, testing or calibration.
Press
5
to toggle between
ACTIVE
and
OFF
.
Press
4
or
6
to scroll to between VR2 and ATPM.
$
$
$
$
$
$
Version 1.20