PULSE Installation, Commissioning and Servicing Manual - Revision 19
21
QUICK REFERENCE GUIDE - VERSION 1�11
Entering Service Mode
Hold FILL 3 seconds
Enter Password FILL (* displayed)
2 – 8 scroll between options
4 – 6 scroll between settings
5 Changes setting
FILL = Enter
Press CLR 3 seconds to exit
Checking Input Status
In Stack Mode, press FILL to view INPUTS
INPUT 1 – Fuelpoint 1 Nozzles (front, key on left)
Lifting each nozzle opens the switch 0=OFF 1=ON
Press FILL for next inputs
INPUT 2 – Fuelpoint 2 Nozzles (rear, key on right)
INPUT 3 – Aux inputs (high flow/float switches)
INPUT 4 – VR inputs (10 = OK, 00, 01 or 11 indicates a
fault)
$
L
$
L
$
L
1 2 3
4 5 6
7 8
9
C
0
FILL
$
L
front valve
flow rate 24
/min
valve open 50%
motor rear valve
front valve
nozzle switch
open
VR2 A VR2 B
POS Enable/Disable
(for standalone)
Comms must be isolated for standalone
Press 5 to change
1 = POS enabled, 0 = Standalone
Press 4 or 6 to scroll to fuelpoint
Repower pump to enable
POS will re-enable when cable is re-connected
Reload configuration
(config zero)
Safely remove the SD card
Place the card in a computer, open config folder
Rename config file by adding a zero to the end
eg: config is renamed as config0
Replace card in dispenser and repower
Memory is cleared and config is reloaded
Re-enter pump numbers, check other settings
Set Hoses Active
Press 5 to change, 0=OFF 1=ON
VR Control Active/Inactive
Press 5 to change
Set Price
FILL enter price FILL press 6 to change Fuelpoint
Only works in Standalone mode
Stack Test
Scroll to STACK 1000
Press 4 or 6 to scroll to other
stacks where present
Press FILL to enter Stack Mode
Press FILL to view next grade
Motor on = press 1
Front valve open = press 3
Rear valve open
= press 9
Setting Flow Rates
(setting a % open for each valve)
In Stack Test Mode
Large number in top row shows valve %
To change, motor and valve(s) must be on
Press 1 for motor, 3 for front valve, 9 for rear valve
Open nozzle, wait till flow rate stabilises
Press 4 to increase by 1%, press 6 to decrease by 1%
Watch flow rate, adjust % to achieve desired rate (eg:
38L/min)
Press 5 to store the % value for this valve
Press FILL for next grade, and repeat
Change Fuelpoint ID
(set pump numbers)
Scroll using 2 or 8 to CGFPID FP1 (Fuelpoint 1)
Press FILL, enter the desired number (eg: 7)
Then press the FILL to set
Scroll using keys 4 or 6 to other fuelpoints and repeat
5/6 Digit Setting
1 = 5 Digit, 0 = 6 Digit, Press 5 to change, FILL to set
Repower dispenser to action the change
Firmware upgrade
New Firmware must be on SD card in Firmware folder
Central Controller
eg: Firmware\11113.CC_
Central Controller
eg: Firmware\11139.LCC
Stack Controller eg: Firmware\11106.LSC
User Interface eg: Firmware\11106.UI_
Insert and unlock SD card
Scroll using 2 or 8 to FIRMW
Display shows the current installed version
Press 4 or 6 to select item to upgrade
Press 5 , then 5 to start, BUSY is displayed
Wait, then check new version is showing
Repeat for all firmware items to be upgraded
Set Time/Date
Scroll to Time or Date
Press FILL, enter time/date, press FILL (if required)
Safe Removal of SD Card
Enter service mode, screen shows ‘SD Card Active’
Press 5, screen shows ‘SD Card Locked’
Now safe to remove, dispenser will operate with card
out though this is not recommended