114
Upgrade and Maintenance Manual
RX300
S7
Basic software procedures
I
For more detailed information on installing ServerView agents, refer to
the "ServerView Operations Manager - Installation ServerView Agents
for Windows" user guide.
5.2.20 Performing a fan test after replacing a defective fan
After replacing a defective system fan or power supply unit containing a
defective fan, the fan error indicators will stay lit until the next fan test. By
default, a fan test is automatically started every 24 hours. The first automatic fan
test being performed after replacing a fan will turn off the fan error indicator.
If you want to start the fan test manually, you can do so by following the
description below:
Executing the fan test via the iRMC Web interface
Ê
Log into the iRMC web interface.
Ê
Under
Sensors
select
Fans
.
Ê
Select the replaced fan in the system fans group and click
Start Fan Test
.
I
For detailed information on iRMC settings, refer to the "Integrated
Remote Management Controller" user guide.
Executing the fan test via ServerView Operations Manager
Ê
Open the ServerView Operations Manager and log in.
Ê
Under
Administration
select
Server Configuration
.
Ê
In the hierarchy tree of the
Server list
tab, select the server to be configured.
Ê
In the right-hand side of the window, specify the details on the selected
server and confirm your entries by clicking
GO...
.
In the left-hand section of the window, the
Configuration
tab is being
activated.
Ê
In the navigation area of the
Configuration
tab, select
Other Settings
.
Ê
Under
Daily Fan Test
, set the daily fan test time to a few minutes from the
current time. (Ensure to note down your previous setting.)
Ê
Click
Save Page
.
The fan test will be started at the specified time.
Summary of Contents for PRIMERGY RX300 S7
Page 6: ...Upgrade and Maintenance Manual RX300 S7 ...
Page 26: ...26 Upgrade and Maintenance Manual RX300 S7 ...
Page 30: ...30 Upgrade and Maintenance Manual RX300 S7 Introduction ...
Page 42: ...42 Upgrade and Maintenance Manual RX300 S7 Before you start ...
Page 116: ...116 Upgrade and Maintenance Manual RX300 S7 Basic software procedures ...
Page 136: ...136 Upgrade and Maintenance Manual RX300 S7 Power supply ...
Page 176: ...176 Upgrade and Maintenance Manual RX300 S7 Hard disk drives solid state drives ...
Page 186: ...186 Upgrade and Maintenance Manual RX300 S7 System fan ...
Page 334: ...334 Upgrade and Maintenance Manual RX300 S7 Processors ...
Page 406: ...406 Upgrade and Maintenance Manual RX300 S7 Accessible drives ...
Page 498: ...498 Upgrade and Maintenance Manual RX300 S7 System board and components ...
Page 524: ...524 Upgrade and Maintenance Manual RX300 S7 Conversion configurations ...
Page 560: ...560 Upgrade and Maintenance Manual RX300 S7 Appendix ...