82
Upgrade and Maintenance Manual
RX300
S7
Basic hardware procedures
Connecting the server to the direct current (optional DC hot-plug power
supply unit)
Figure 23: Connecting the server to the dc voltage
Ê
Connect the power cord with the connector to the power supply unit of the
server (1).
Ê
Attach the connector with the 2 screws (2).
Ê
Connect the wire labeled "Ground" to an appropriate earth ground.
Ê
Connect the other two wires of the power cable to the current bar on the rack
(see Technical Manual of the rack).
4.10 Switching on the server
V
CAUTION!
●
Before switching on the server, make sure the server cover is closed.
In order to comply with applicable EMC regulations (regulations on
electromagnetic compatibility) and satisfy cooling requirements, the
PRIMERGY RX300 S7 server must not run while the server cover is
removed.
Summary of Contents for PRIMERGY RX300 S7
Page 6: ...Upgrade and Maintenance Manual RX300 S7 ...
Page 26: ...26 Upgrade and Maintenance Manual RX300 S7 ...
Page 30: ...30 Upgrade and Maintenance Manual RX300 S7 Introduction ...
Page 42: ...42 Upgrade and Maintenance Manual RX300 S7 Before you start ...
Page 116: ...116 Upgrade and Maintenance Manual RX300 S7 Basic software procedures ...
Page 136: ...136 Upgrade and Maintenance Manual RX300 S7 Power supply ...
Page 176: ...176 Upgrade and Maintenance Manual RX300 S7 Hard disk drives solid state drives ...
Page 186: ...186 Upgrade and Maintenance Manual RX300 S7 System fan ...
Page 334: ...334 Upgrade and Maintenance Manual RX300 S7 Processors ...
Page 406: ...406 Upgrade and Maintenance Manual RX300 S7 Accessible drives ...
Page 498: ...498 Upgrade and Maintenance Manual RX300 S7 System board and components ...
Page 524: ...524 Upgrade and Maintenance Manual RX300 S7 Conversion configurations ...
Page 560: ...560 Upgrade and Maintenance Manual RX300 S7 Appendix ...