CAUTION
▶
When replacing a PSU in a non-redundant PSU configuration, the
server must be switched off first.
▶
Replace the PSU after specifying the one that breaks down at work
by revitalization.
Note for servers using CMA (Cable Management Arm)
Regarding of removing PSUs, additional tasks are needed, due to an
interference between CMA and the PSUs.
▶
Push the lock spring inward to unlock the CMA bracket, see
.
▶
Remove the CMA.
▶
Hold the CMA including cables in the one hand.
▶
Remove the PSU (see
) and install the new PSU carefully.
Note for PSU 1:
Remove the PSU 1 carefully while lifting PSU 1 and bringing PSU 1
to the right, in order to avoid interference.
▶
Mount the complete assembly (CMA bracket and the CMA) again into the
rail.
Preliminary steps
▶
"Locating the defective server" on page 45
▶
Check which PSU is defective.
PSU is defective when the PSU status indicator lights orange. For more
information, see
"Indicator on hot-plug PSU" on page 422
▶
Only when replacing a PSU in a non-redundant configuration:
▶
Remove the power cord from the defective PSU, see
Removing the defective hot-plug PSU
▶
Remove the PSU, see
"Removing a hot-plug PSU" on page 113
.
Power supply unit (PSU)
RX2530 M6
Upgrade and Maintenance Manual
115
Summary of Contents for PRIMERGY RX2530 M5
Page 18: ...Content Upgrade and Maintenance Manual RX2530 M6 ...
Page 194: ...Fans 194 Upgrade and Maintenance Manual RX2530 M6 ...
Page 262: ...Expansion cards and backup units 262 Upgrade and Maintenance Manual RX2530 M6 ...
Page 278: ...Main memory 278 Upgrade and Maintenance Manual RX2530 M6 ...
Page 324: ...Accessible drives 324 Upgrade and Maintenance Manual RX2530 M6 ...
Page 336: ...Front panel 336 Upgrade and Maintenance Manual RX2530 M6 ...
Page 344: ...Serial interface 344 Upgrade and Maintenance Manual RX2530 M6 ...
Page 480: ...List of all used screws for PRIMERGY Servers Assembled in Germany and Japan February 2019 ...