16.4.5
Replacing the TPM
Field Replaceable Unit
(FRU)
Hardware: 35 minutes
Tools:
Removing the system board:
– Phillips PH2 / (+) No. 2 screw driver
– Torx 30 screw driver
Replacing the TPM:
– Bit screw driver
– TPM bit insert
(*)
– flat nose pliers
– thin slotted screw driver (2 x 0.4 mm)
(*)
(*)
For Japan:
– Dedicated TPM screw driver (CWZ8291A)
– TPM module fixing tool (S26361-F3552-L909)
CAUTION
▶
Advise your contact persons that they must provide you with all
recovery keys which belong to the system to restore them in the
TPM later.
Preliminary steps
▶
"Locating the defective server" on page 45
.
▶
"Suspending BitLocker functionality" on page 75
.
▶
If applicable,
"Removing the front cover with lock" on page 48
▶
"Shutting down the server" on page 48
▶
"Disconnecting the power cord" on page 49
▶
"Removing a hot-plug PSU" on page 113
.
System board and components
358
Upgrade and Maintenance Manual
RX2530 M6