CX2550/60/70 M4
Upgrade and Maintenance Manual
149
Expansion cards and OCP mezzanine cards
6.4.3
Removing the FBU
V
CAUTION!
Do not throw backup units into the trash can. Batteries must be disposed
of in accordance with local regulations concerning special waste.
For further safety information, see section
.
6.4.3.1
Preliminary steps
Ê
"Disabling the boot watchdog functionality of ServerView Operations
Manager" on page 73
Ê
Locate the desired server node with the ID button.
Ê
"Shutting down the server node" on page 50
Ê
Remove all external cables from the server node.
Ê
"Removing the server node from the server enclosure" on page 51
Ê
"Removing the memory slot air duct (Air cooling only)" on page 63
Ê
Remove the riser module next to that one with the RAID card, see section
"Removing the riser module" on page 58
Upgrade and Repair Unit
(URU)
Hardware: 5 minutes
Tools:
tool-less
Summary of Contents for PRIMERGY CX2550 M4
Page 6: ...6 Upgrade and Maintenance Manual CX2550 60 70 M4 ...
Page 20: ...Upgrade and Maintenance Manual CX2550 60 70 M4 Contents ...
Page 46: ...46 Upgrade and Maintenance Manual CX2550 60 70 M4 Important information ...
Page 70: ...70 Upgrade and Maintenance Manual CX2550 60 70 M4 Basic hardware procedures ...
Page 114: ...114 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 182: ...182 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 192: ...192 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory Figure 85 Memory dummy module ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory ...
Page 320: ...320 Upgrade and Maintenance Manual CX2550 60 70 M4 System board and components ...
Page 356: ...356 Upgrade and Maintenance Manual CX2550 60 70 M4 GPGPU extension tray ...
Page 418: ...418 Upgrade and Maintenance Manual CX2550 60 70 M4 SXM2 extension tray ...
Page 454: ...454 Upgrade and Maintenance Manual CX2550 60 70 M4 Appendix ...