CX2550/60/70 M4
Upgrade and Maintenance Manual
405
SXM2 extension tray
11.3
Replacing the SXM2 LC
11.3.1 Preliminary steps
Perform the following procedures:
Ê
"Disabling the boot watchdog functionality of ServerView Operations
Manager" on page 73
Ê
Locate the desired server node with the ID button.
Ê
"Shutting down the server node" on page 50
Ê
If applicable, remove all external cables from the server node.
Ê
"Removing the server node from the server enclosure" on page 51
11.3.2 Replacing the SXM2 LC
Ê
Remove the SXM2 LC, see section
"Removing liquid cooling (LC)" on
Ê
Apply thermal paste to the SXM2 surface, see section
.
Ê
Install the SXM2 LC, see section
"Installing liquid cooling (LC)" on page 379
11.3.3 Concluding steps
Perform the following procedures:
Ê
"Installing the server node in the server enclosure" on page 67
Ê
If applicable, connect all external cables to the server node.
Field Replaceable Unit
(FRU)
Hardware: 15 minutes
Tools:
Preliminary and concluding steps: tool-less
Main steps: PH2 / (+) No. 2 screw
Summary of Contents for PRIMERGY CX2550 M4
Page 6: ...6 Upgrade and Maintenance Manual CX2550 60 70 M4 ...
Page 20: ...Upgrade and Maintenance Manual CX2550 60 70 M4 Contents ...
Page 46: ...46 Upgrade and Maintenance Manual CX2550 60 70 M4 Important information ...
Page 70: ...70 Upgrade and Maintenance Manual CX2550 60 70 M4 Basic hardware procedures ...
Page 114: ...114 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 182: ...182 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 192: ...192 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory Figure 85 Memory dummy module ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory ...
Page 320: ...320 Upgrade and Maintenance Manual CX2550 60 70 M4 System board and components ...
Page 356: ...356 Upgrade and Maintenance Manual CX2550 60 70 M4 GPGPU extension tray ...
Page 418: ...418 Upgrade and Maintenance Manual CX2550 60 70 M4 SXM2 extension tray ...
Page 454: ...454 Upgrade and Maintenance Manual CX2550 60 70 M4 Appendix ...