CX2550/60/70 M4
Upgrade and Maintenance Manual
347
GPGPU extension tray
Ê
Place the GPGPU tray so that the system board connector of the riser (see
oval) is not damaged.
Ê
Disconnect the I2C cable from the riser (see arrow).
Ê
Remove four screws from the outside of the chassis in the order of
numbering (1 - 4).
Ê
Remove the riser in a vertical motion out of the chassis.
10.9.3 Installing the GPGPU riser
Figure 229: Installing the riser (R)
Ê
Insert the riser in a vertical motion in the chassis.
V
Ensure that the system board connector of the riser (see oval) is not
damaged.
Ê
secure the riser with four screws from the outside of the chassis in the order
of numbering (1 - 4).
Ê
Connect the I2C cable to the riser (see arrow).
10.9.4 Concluding steps
Perform the following procedures:
Summary of Contents for PRIMERGY CX2550 M4
Page 6: ...6 Upgrade and Maintenance Manual CX2550 60 70 M4 ...
Page 20: ...Upgrade and Maintenance Manual CX2550 60 70 M4 Contents ...
Page 46: ...46 Upgrade and Maintenance Manual CX2550 60 70 M4 Important information ...
Page 70: ...70 Upgrade and Maintenance Manual CX2550 60 70 M4 Basic hardware procedures ...
Page 114: ...114 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 182: ...182 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 192: ...192 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory Figure 85 Memory dummy module ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory ...
Page 320: ...320 Upgrade and Maintenance Manual CX2550 60 70 M4 System board and components ...
Page 356: ...356 Upgrade and Maintenance Manual CX2550 60 70 M4 GPGPU extension tray ...
Page 418: ...418 Upgrade and Maintenance Manual CX2550 60 70 M4 SXM2 extension tray ...
Page 454: ...454 Upgrade and Maintenance Manual CX2550 60 70 M4 Appendix ...