CX2550/60/70 M4
Upgrade and Maintenance Manual
289
System board and components
9.3.2.3
Concluding steps
Ê
"Installing the system board" on page 311
Ê
"Completing the system board" on page 317
Ê
"Installing the server node in the server enclosure" on page 67
Ê
If applicable, reconnect all external cables.
Ê
"Enabling SVOM boot watchdog functionality" on page 88
9.3.3
Replacing the TPM
V
CAUTION!
Advise your contact persons that they must provide you with all recovery
keys which belong to the system to restore them in the TPM later.
The spare parts act as TPM2.0. For the use as TPM1.2, the customer
need to update the firmware to TPM1.2 after replacement. For firmware,
please see below.
http://ts.fujitsu.com/support/
http://www.fujitsu.com/jp/products/computing/servers/primergy/downloads/
(for Japan)
Field Replaceable Unit
(FRU)
Hardware: 30 minutes
Tools:
Removing the system board:
– Phillips PH2 / (+) No. 2 screw driver
Replacing the TPM:
– Bit screw driver
– TPM bit insert
(
*
)
– thin slotted screw driver (2 x 0.4 mm)
(
*
)
(
*
)
For Japan:
– Dedicated TPM screw driver (CWZ8291A)
– TPM module fixing tool (S26361-F3552-L909)
Summary of Contents for PRIMERGY CX2550 M4
Page 6: ...6 Upgrade and Maintenance Manual CX2550 60 70 M4 ...
Page 20: ...Upgrade and Maintenance Manual CX2550 60 70 M4 Contents ...
Page 46: ...46 Upgrade and Maintenance Manual CX2550 60 70 M4 Important information ...
Page 70: ...70 Upgrade and Maintenance Manual CX2550 60 70 M4 Basic hardware procedures ...
Page 114: ...114 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 182: ...182 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 192: ...192 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory Figure 85 Memory dummy module ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory ...
Page 320: ...320 Upgrade and Maintenance Manual CX2550 60 70 M4 System board and components ...
Page 356: ...356 Upgrade and Maintenance Manual CX2550 60 70 M4 GPGPU extension tray ...
Page 418: ...418 Upgrade and Maintenance Manual CX2550 60 70 M4 SXM2 extension tray ...
Page 454: ...454 Upgrade and Maintenance Manual CX2550 60 70 M4 Appendix ...