364
Upgrade and Maintenance Manual
CX2550/60/70 M4
SXM2 extension tray
Figure 244: Removing LC heat sinks from SXM2 modules 3 (A) and 4 (B)
Ê
Loosen the captive screws of SXM2 module 4 (B) (see circles) following the
sequence described below and using a #2 screwdriver:
V
CAUTION
Please don’t use an electric screwdriver.
1. Loosen the four captive screws one by one (in the sequence 4 to 1)
rotating them a half-turn each.
2. Loosen the captive screws 4 and 3 rotating them two or three turns each.
3. Repeat the step 2 until the screws 4 and 3 are completely loosened.
4. Loosen the captive screws 2 and 1 rotating them two or three turns each.
5. Repeat the step 2 until the screws 2 and 1 are completely loosened.
Ê
Repeat the procedure for SXM2 module 3 (A).
Ê
Remove the LC heat sinks.
I
If the LC heat sinks of SXM2 modules 1 and 2 are not to be replaced, the
steps described in the next section are not necessary.
Summary of Contents for PRIMERGY CX2550 M4
Page 6: ...6 Upgrade and Maintenance Manual CX2550 60 70 M4 ...
Page 20: ...Upgrade and Maintenance Manual CX2550 60 70 M4 Contents ...
Page 46: ...46 Upgrade and Maintenance Manual CX2550 60 70 M4 Important information ...
Page 70: ...70 Upgrade and Maintenance Manual CX2550 60 70 M4 Basic hardware procedures ...
Page 114: ...114 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 182: ...182 Upgrade and Maintenance Manual CX2550 60 70 M4 Expansion cards and OCP mezzanine cards ...
Page 192: ...192 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory Figure 85 Memory dummy module ...
Page 204: ...204 Upgrade and Maintenance Manual CX2550 60 70 M4 Main memory ...
Page 320: ...320 Upgrade and Maintenance Manual CX2550 60 70 M4 System board and components ...
Page 356: ...356 Upgrade and Maintenance Manual CX2550 60 70 M4 GPGPU extension tray ...
Page 418: ...418 Upgrade and Maintenance Manual CX2550 60 70 M4 SXM2 extension tray ...
Page 454: ...454 Upgrade and Maintenance Manual CX2550 60 70 M4 Appendix ...