Check Point 2 : Wire installation wrong remote controller group setting
•
Wrong wire connection in remote controller group (Please refer to the installation manual)
•
The number of connecting indoor unit and remote controller in one remote controller group
were less than 16 units.
↓
Check Point 2-1 : Check Indoor unit main PCB
•
Check if main PCB damage
•
Change main PCB and check the error after setting remote controller address
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-10) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING