2-26. E: 84. Current sensor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 84
Detective actuator
Outdoor unit
main PCB
When input current sensor has detected 0 A, while
inverter compressor is operating at higher than 50 rps,
after 1 minute upon starting the compressor. (Except
during the defrost operation)
Forecast of cause
Defective connection of electric components
External cause
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
↓
Check point 2. Check connections of outdoor
unit electrical components
Upon correcting the removed connector or mis-
wiring, reset the power.
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom,
change main PCB.
↓
End
Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
End
2-26. E: 84. Current sensor error (Outdoor unit)
- (03-33) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...