2-29. E: 94. Trip detection (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 94
Detective actuator
Outdoor unit
Inverter PCB
Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE:
The number of generations is reset when the
compressor starts up.
Main PCB
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Inverter PCB
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
•
No obstructions in air passages?
•
Heat exchange fins clogged
•
Outdoor unit fan motor check
•
Ambient temperature not raised by the effect of other heat sources?
•
Discharged air not sucked in?
↓
Check point 2. Replace inverter PCB
If Check point 1 do not improve the symptom, change inverter PCB.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
↓
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
↓
End
2-29. E: 94. Trip detection (Outdoor unit)
- (03-36) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...