2-6. E: 26. Address setting error in wired remote controller
(Indoor unit)
Indicator
Wired remote
controller
Error code
E: 26
Detective actuator
Wired remote controller (2-wire)
•
When the address number set by auto setting and
manual setting are mixed in one remote controller
group
•
When the duplicated address number exists in one
remote controller group
Indoor unit controller PCB
Forecast of cause
Wrong wiring of remote controller group
Wrong remote controller address setting
Indoor unit main PCB failure
Remote controller failure
Check point 1. Wire installation
•
Check the wire connection in the remote controller group (For installation method, refer to in-
stallation manual)
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
↓
Check point 2. Wrong remote controller group setting
•
The given address number by auto setting (00) and the manual set number (except 00) are not
existing in one remote controller group.
•
The remote controller address setting by UI is not existing same address.
•
The duplicate address number is not existing in one remote controller group.
↓
Check point 3. Check indoor unit main PCB
•
Check if main PCB is damaged.
•
Change main PCB and check the error after setting remote controller address.
↓
End
2-6. E: 26. Address setting error in wired remote controller (Indoor unit)
- (03-13) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...