2-19. E: 64. PFC circuit error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 64
Detective actuator
Outdoor unit
Main PCB
•
When inverter input DC voltage is higher than 420
V for over 3 seconds, the compressor stops.
•
If the same operation is repeated 5 times, the
compressor stops permanently.
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 2. Check connection of Connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace main PCB
If check point 1 to 2 do not improve the symptom, change main PCB.
↓
End
2-19. E: 64. PFC circuit error (Outdoor unit)
- (03-26) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...