3-2. Outdoor unit—No power
Forecast of cause
Power supply failure
External cause
Electrical components defective
Check point 1. Check installation condition
•
Is the circuit breaker on or off?
•
Check loose or removed connection cable.
→ If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN &
TECHNICAL MANUAL”.
↓
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 198 to 264 V appears at outdoor unit terminal L — N
→ If no, go to
and
.
+
-
↓
•
Check fuse in main PCB.
If fuse is open, check if the wiring between terminal and main PCB is loose, and replace fuse.
↓
Check point 4. Replace main PCB
If check point 1 to 3 do not improve the symptom, change main PCB.
↓
End
3-2. Outdoor unit—No power
- (03-50) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...