2-20. E: 65. Trip terminal L error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 65
Detective actuator
Outdoor unit
Main PCB
When the signal from FO terminal of IPM is “L” (0 V)
during the compressor stopping.
Forecast of cause
Main PCB failure
Check point 1. Check main PCB
Replace the outdoor unit main PCB.
↓
End
2-20. E: 65. Trip terminal L error (Outdoor unit)
- (03-27) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING