2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Wired remote
controller
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
•
3-wire type: 1 minute
•
2-wire type: 2.5 minutes
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
•
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
↓
Check Point 1-2 : Check Wired remote controller and main PCB
[AU type]
Check voltage at CN14 of main PCB (terminal 1—3, terminal 1—2). (Power supply to the remote
controller)
•
If it is DC 12 V, remote controller is failure. (Main PCB is normal)
–
Replace remote control
•
If it is DC 0 V, main PCB is failure. (Check remote controller once again)
–
Replace main PCB
[AR type]
Check voltage at CN300 of main PCB (terminal 1—3, terminal 1—2). (Power supply to the remote
controller)
•
If it is DC 13 V, remote controller is failure. (Main PCB is normal)
–
Replace remote control
•
If it is DC 0 V, main PCB is failure. (Check remote controller once again)
–
Replace main PCB
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-9) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...