2-8. E: 32. Indoor unit main PCB error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 32
Detective actuator
Indoor unit
main PCB
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Forecast of cause
External cause
Defective connection of electric components
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
→ If no, go to
↓
Check point 2. Check Indoor unit electric components
•
Check all connectors. (loose connector or incorrect wiring)
•
Check any shortage or corrosion on PCB.
↓
Check point 3. Replace main PCB
Change main PCB.
↓
End
Check point 1-2. Check external cause such as noise
•
Check if the ground connection is proper.
•
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
↓
End
NOTE: EEPROM
EEPROM (Electronically Erasable and Programmable Read Only Memory) is a non-volatile
memory which keeps memorized information even if the power is turned off. It can change
the contents electronically. To change the contents, it uses higher voltage than normal, and
it cannot change a partial contents. (Rewriting shall be done upon erasing the all contents.)
There is a limit in a number of rewriting.
2-8. E: 32. Indoor unit main PCB error (Indoor unit)
- (03-15) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...