17. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRIDE PREVENTION CONTROL
Discharge gas thermosensor (discharge thermistor : Outdoor side)
detects discharge gas temperature.
AOUG36LMAS1
AOUG48LMAS1
AOU24RGLX
AOU30RGLX
When discharge temperature exceeds 219
.2˚
F (104.0
˚
C),
compressor frequency is decreased 30rps,
and it continues to decrease 30 rps every 120 seconds
until temperature dips from 219.2
˚
F (104
.0˚
C)
When discharge temperature dips from 213
.8˚
F (101.0
˚
C),
control of compressor frequency is released.
When discharge temperature exceeds 230.0
˚
F (110.0
˚
C),
compressor stops and indoor unit LED starts blinking.
When discharge temperature exceeds 219.2
˚
F (104
.0˚
C),
compressor frequency is decreased 10rps,
and it continues to decrease 10 rps every 120 seconds
until temperature dips from 219.2
˚
F (104.0
˚
C)
When discharge temperature dips from 213.8
˚
F (101
.0˚
C),
control of compressor frequency is released.
When discharge temperature exceeds 230
.0˚
F (110.0
˚
C),
compressor stops and indoor unit LED starts blinking.
04-31