2. CURRENT RELEASE CONTROL
AOU24RGLX
AOU30RGLX
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
Current release operation value / Release value
11.0A/ 10.5A
13.0A/ 12.5A
15.0A/ 14.5A
15.0A/14.5A
62.6°F(17°C)
53.6°F(12°C)
41°F(5°C)
OT (Control / Release)
AOU24/30RGLX
Heating
Cooling
OT (Control / Release)
10.0A/ 9.5A
13.0A/ 12.5A
14.5A/ 14.0A
114.8°F(46°C)
104°F(40°C)
14.5A/ 14.0A
53.6°F(12°C)
14.5A/ 14.0A
35.6°F(2°C)
AOU24/30RGLX
122°F(50°C)
9.0A/ 8.5A
OT : Outdoor temperature