![Fujitsu AMUG24LMAS Service Manual Download Page 167](http://html.mh-extra.com/html/fujitsu/amug24lmas/amug24lmas_service-manual_118226167.webp)
3-3. Pump down
WARNING
During the pump down operation, make sure that compressor is off before you remove the refriger-
ant piping. Do not remove the connection pipe while the compressor is in operation with valve
open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even
injury.
¢
Pump down operation
When moving or discarding the air conditioner, in order to consider the environment and avoid the
discharge of refrigerant to the atmosphere, pump down according to the following procedure.
1. Connect the pressure gauge to the charging port.
2. Change the DIP switch on the board (SET1-2) to On*1
*Be sure the power supply is disconnected on the breaker is turned off when changing the DIP
switch.
*1: DIP switch
(SET1-2)
ON
1 2 3 4
SET1
3. To start operation, press the [PUMP DOWN] switch*2 for 3 seconds or press after the power
has been on for 3 min.
PUMP DOWN
1
W
S
TEST
RUN
*2: Push switch (SW1)
During pump down, the LED (POWER/MODE) will flash 3 times consecutively.
(3-blink)
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
NOTE:
If the [PUMP DOWN] switch is pressed during compressor operation, the compres-
sor will stop, and the operation will start after about 3 min.
4. Close the liquid pipe valve.
5. When the value between 7.3 psi and 0 psi (0.05 Mpa to 0 Mpa) is shown, close the gas pipe
valve.
6. Stop pump down by pressing the [PUMP DOWN] switch for 3 seconds.
The LED will light as follows.
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
(3-blink)
3-3. Pump down
- (05-19) -
3. Test
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...