![Fujitsu AMUG24LMAS Service Manual Download Page 193](http://html.mh-extra.com/html/fujitsu/amug24lmas/amug24lmas_service-manual_118226193.webp)
Auxiliary heat pump control
•
External heater output
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating
temperature.
Heater off
DIP-SW101-3
On
•
Heater is off as shown in following diagram of heating
temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
•
Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3
Off
•
Heater is off as shown in following diagram of heating
temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
– Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.5 °C)
– Temperature of heater off: Set temperature (Ts) + 0.9 °F (+ 0.5 °C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
Tr-Ts ≥ 0.9°F
(0.5°C)
•
Auxiliary heat pump On/Off
– Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of heat pump).
– All control temperatures will shift by adjusting “Thon”.
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
*
Tr-Ts
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts (=Thon) < -5.4°F (-3°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
4-4. Details of function
- (05-45) -
4. External input and output
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...