Troubleshooting 33
Forecast of cause:
Check Point 2 :
Check external cause at indoor and outdoor (voltage drop or noise)
Check Point 1 :
Check indoor and outdoor installation condition
OK
OK
OK
OK
OK
No operation (Power is ON)
1. Setting / connection failure
2. External cause
3. Electrical component defective
4. Communication error between controller PCB
and wired remote control
Indoor unit - Check incorrect wiring between indoor unit and remote control.
Or, check if there is an open cable connection.
Are these indoor unit, outdoor unit, and remote control suitable model numbers to connect?
>> If there is some abnormal condition,correct it by referring to Installation manual and
Data & Technical Manual.
Turn off power and check/ correct followings.
Is there loose or removed
communication line of indoor unit and outdoor unit?
Instant drop -----
Check if there is a large load electric apparatus in the same circuit.
Momentary power failure -----
Check if there is a defective contact or leak current in the power supply circuit.
Noise -----
Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
03-45
Check Point 3 :
Check wired remote control (2 wire type)
Check Point 3 :
Check wired remote control and controller PCB
>> If it is DC12V, remote control is failure.
(Controller PCB is normal)
Replace remote control
>> If it is DC 0V, controller PCB is failure.
(Check remote control once again)
Replace controller PCB
Check voltage at CN300 of controller PCB.
(Power supply to remote control)
If the connection condition is normal,
replace the wired remote control.
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...