10) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number
Setting value
Setting description
Factory setting
60
00
Operation status
♦
09
Error status
10
Indoor unit fan operation status
11
External heater
11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to “External heater output” in
Chapter 4-4. "Details of function"
Function
number
Setting value
Setting description
Factory
setting
61
00
Auxiliary heater control 1
♦
01
Auxiliary heater control 2
02
Heat pump prohibition control
03
Auxiliary heater control by outdoor temperature 1
04
Auxiliary heater control by outdoor temperature 2
05
Auxiliary heater control by outdoor temperature 3
06
Auxiliary heat pump control
07
Auxiliary heat pump control by outdoor temperature 1
08
Auxiliary heat pump control by outdoor temperature 2
09
Auxiliary heat pump control by outdoor temperature 3
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in
Chapter 4-4. "Details of function"
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00
01 to 09
Heater: On
Heater: Off
Heater: On
Heater: Off
62
00
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
-0.9 °F (-0.5 °C)
0.9 °F (0.5 °C)
♦
01
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
0.9 °F (0.5 °C)
02
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
-3.6 °F (-2 °C)
0.9 °F (0.5 °C)
03
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
-5.4 °F (-3 °C)
0.9 °F (0.5 °C)
04
-7.2 °F (-4 °C)
-1.8 °F (-1 °C)
-7.2 °F (-4 °C)
0.9 °F (0.5 °C)
05
-9.0 °F (-5 °C)
-1.8 °F (-1 °C)
-9.0 °F (-5 °C)
0.9 °F (0.5 °C)
06
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
-0.9 °F (-0.5 °C)
0 °F (0 °C)
07
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
-1.8 °F (-1 °C)
0 °F (0 °C)
08
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
-3.6 °F (-2 °C)
0 °F (0 °C)
09
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
-5.4 °F (-3 °C)
0 °F (0 °C)
10
-7.2 °F (-4 °C)
-0.9 °F (-0.5 °C)
-7.2 °F (-4 °C)
0 °F (0 °C)
11
-9.0 °F (-5 °C)
-0.9 °F (-0.5 °C)
-9.0 °F (-5 °C)
0 °F (0 °C)
12
-5.4 °F (-3 °C)
0 °F (0 °C)
-0.9 °F (-0.5 °C)
-0.9 °F (-0.5 °C)
13
-3.6 °F (-2 °C)
0 °F (0 °C)
-1.8 °F (-1 °C)
-0.9 °F (-0.5 °C)
14
-3.6 °F (-2 °C)
0 °F (0 °C)
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
15
-5.4 °F (-3 °C)
0 °F (0 °C)
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
16
-7.2 °F (-4 °C)
0 °F (0 °C)
-7.2 °F (-4 °C)
-0.9 °F (-0.5 °C)
17
-9.0 °F (-5 °C)
0 °F (0 °C)
-9.0 °F (-5 °C)
-0.9 °F (-0.5 °C)
1-2. Function settings by using remote controller
- (05-6) -
1. Function settings (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...