Troubleshooting 10
Indoor unit communication circuit (WRC) error
Indicate or Display:
Indoor unit
Operation lamp: 3 timesFlash,
Timer lamp : 10times Flash
Wired remote control
Error code : [E : 3A]
Detective actuators:
Wired remote control (2-wire)
Indoor unit controller PCB circuit
Detective details:
When the indoor unit(s) detects the configuration of RCG abnormal or
the indoor unit detects lack of primary -remote control.
Check Point 2 , 3: Check Indoor unit controller PCB
Forecast of cause:
1. Terminal connection abnormal
2. Wired remote control failure
3. Indoor unit controller PCB defective
Check Point 1 : Check the connection of terminal
Indoor unit - Check the connection of terminal between
remote control and indoor unit, or between indoor units and
check if there is a disconnection or short of the cable
Check terminal voltage of controller PCB connector CN300 (Power supply for remote controller)
If DC12V, Remote control failure (Controller PCB is OK) >>> Replace remote controller
If DC0V, Controller PCB failure (Remote is OK) >>> Replace controller PCB
In case of re-installation is done due to removed connector or incorrect wiring,
turn on the power again.
After turning off the power supply, check & correct the followings
03-15
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
5
15
Outdoor unit (AOUG36/48LMAS1)
A
B
F
E
D
C
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...