3. AUTO CHANGEOVER OPERATION
04-09
When operation starts, indoor fan and outdoor fan are operated for around 1 minutes.
Room temperature and outdoor temperature are sensed, and the operation mode is selected
in accordance with the table below.
<Monitoring mode>
Operation mode selection table
Room temperature (TR)
TR > Ts+ 3.6°F (2°C)
Ts + 3.6°F (2°C)
≥
TR
≥
Ts - 3.6°F (2°C)
*
Middle zone
TR < Ts - 3.6°F (2°C)
Heating
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the Cooling or Heating mode was selected at above, operation is switched
to Monitoring and the operation mode is selected again.
When the middle zone is selected on the predetermining of the operation mode, the operation mode
before the changing to the monitor mode is selected.
1
2
3
1
Outdoor temperature zone selection
Cooling
Operation mode
Temperature
77°F (25°C) and over
75.2°F (24°C) and under
Heating
Cooling
Mode
*
If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling and Heating mode,
indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling and Heating mode, indoor unit will be operated
according to the outdoor temperature as below.
TR : Room temperature
Ts : Setting temperature
When AUTO mode is set using a remote control,
optimum operation mode is selected from Heating, Cooling and Monitoring mode.
In operation, optimum mode is automatically switched by temperature changes.
Set temperature can be set between 64°F (18°C) and 86°F (30°C) by 1°F (0.5°C).
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...